INSTALLATION INSTRUCTIONS
101-DE/101-KDE
Features:
Egress Delay
15 or 30 second exit delay
1 or 2 second nuisance delay
Built-In 3 Function keypad
Alarm and lock reset
1 to 30 second bypass
Sustained bypass
Additional keyswitch optional
Control Inputs
1 to 30 second request-to-exit and bypass
input with anti-tailgate and jumper
selectable door prop alarm.
Reset
Built-In Annunciation
Armed mode
Nuisance mode
Irreversible egress mode
Release mode
Digital countdown mode
Field selectable voice notification or tone
Field selectable male voice with security
message or female voice with safety
message
Monitoring Outputs
Armed mode
Egress initiation status
Released status
Optional EMLock Outputs
Door position sensor – indicates door
open and door closed, commonly used to
verify egress after release.
Magnetic bond sensor – indicates locked
with full holding force, low holding force,
unlocked and tampering.
Triggering Options
Egress alarm triggered by door
movement when used with SDC
1500DE series EMLocks.
Trigger input from external device
field selectable (N/O or N/C)
Field selectable automatic or manual
power up after emergency release or
power loss. Use of manual power up
complies with California Building Code
(OSHPD) requirements.
Code Compliance
IFC International fire Code
IBC International Building Code
NFPA 101 Life Safety Code
NFPA 1 Uniform Fire Code
California Building Code
P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd Rev B10 04-13 Page 1
Any suggestions or comments to this instruction or
product are welcome. Please contact us through
our website or email [email protected]
Application:
When unauthorized egress is initiated SDC Exit Check
®
delays egress
through the door for 15 seconds (or 30 seconds). Meanwhile, the person
exiting must wait while personnel or security responds. The door unlocks
after 15 seconds have elapsed permitting egress. When powered by a fire
control supervised power supply, the lock will release immediately in an
emergency. The digital keypad eliminates the need to carry and locate
keys for reset and bypass functions.
Choice of Mounting
Recessed mounted
(3 gang metal plaster ring included)
Surface mounted with optional 3 gang
box (DEC-J)
Optional shroud (SHD-J) to be used with
DEC-J surface box.
Exit Check
®
applications include:
Restricting the egress of wandering patients for their own safety.
Restricting the egress of commercial center patrons for security application needs.
Controlling pedestrian traffic in transportation facilities, including airport jetways
and tarmacs
Reducing Shoplifting and Employee Theft
Display Modes
Door armed and locked.
Alarm countdown has ended,
door is unlocked and alarm sounding
until reset.
Door unlocked and alarm is shunted
(REX or Bypass)
Door has been opened after REX,
Bypass or Alarm.
15
00
--
--
--
--
801 Avenida Acaso, Camarillo, Ca. 93012 • (805) 494-0622
www.sdcsecurity.com • E-mail: service@sdcsecurity.com
Verbal Exit Instructions or
Alarm Tone Only and
Digital Countdown Display
Vedere la pagina 0
1 2 3 4 5 6 ... 11 12

Sommario

Pagina 1 - 101-DE/101-KDE

INSTALLATION INSTRUCTIONS101-DE/101-KDEFeatures:Egress Delay15 or 30 second exit delay1 or 2 second nuisance delayBuilt-In 3 Function keypadAlarm and

Pagina 2 - (BOCA/Chicago)

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd Rev B10 04-13 Page 10RECOMMENDED MOUNTING PROCEDUREAASLIDE PACKING FOAM

Pagina 3

101-DE101-KDEPWRLOCKRED RNO CTRIGREXRESETC NOC NOC NO-+-+Trigger Switch-+345678ToPowerSupplyREMOTEREXREMOTERESETPUSH UNTIL ALARM SOUNDS. DOOR CAN

Pagina 4 - KEY CYLINDER INSTALLATION

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd Rev B10 04-13 Page 12UserNumberNamePINCodeUserNumberNamePINCode

Pagina 5

101-DE/101-KDE Operational DescriptionThe door is closed and secured by latching hardware. The model 101-DE/101-KDE Exit Check controller sends pow

Pagina 6 - MODEL 101-KDE

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd Rev B10 04-13 Page 3Typical System Wiring - Single Door Notes: For more

Pagina 7

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd Rev B10 04-13 Page 4SURFACE MOUNT 3 GANG BOX OVEREXISTING RECESSED 2 GAN

Pagina 8

SURFACE MOUNT3 GANG BOXTO WALL2) Carefully insert unit andsecure with screws supplied.1) Attach optional 3 Gang Surface Mount Box to wall usingscrew

Pagina 9

MODEL 101-DEMODEL 101-KDEP:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd Rev B10 04-13 Page 6CONTROLLER SPECIFICATIONSIN

Pagina 10 - VIEW A-A

Keypad ProgrammingKEYPAD STATUS LEDSFACTORY PROGRAMMED CODES1234 Master Code (default)11Reset22Authorized Exit (Rex)FunctionPin Code33 Bypass (toggle

Pagina 11 - OPENED IN 15 SECONDS

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd Rev B10 04-13 Page 8*Deleting a User (Option 2)To add a user:Press 2#

Pagina 12

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd Rev B10 04-13 Page 9SPECIFICATIONSInputs:Voltage input: Auto sensing 12/